It is built to meet the growing demands in both LV and MV switchgear and controlgear applications ranging from basic stand-alone to more complex system solutions.
The AQ 100 series is designed and tested according to the latest protection relay standards and is hence suitable for installations in any environment, such as utility, power plant, wind-power, off shore, marine, oil and gas, mining, steel or any other heavy industry application and as well commercial and institutional electrical systems. The AQ 100 modular design makes it an excellent candidate for both new and retrofit installations.
AQ-110F | 3 fiber loop sensors, connectivity to arc quenching system, 2 high speed outputs (2ms trip time), 4 trip relays (7ms trip time) *, 1 system failure relay, 1BO, 2BI,
Applicable sensors: AQ 06, AQ 07
AQ-110P | 12 point sensors, 1 fiber loop sensor (optional), connectivity to arc quenching system, 2 high speed outputs (2ms trip time), 4 trip relays (7ms trip time) *, 1 system failure relay, 1BO, 2BI,
Applicable sensors: AQ 01, AQ 01M, AQ 02, AQ 06 (optional), AQ 07 (optional)
AQ-102 | 3 fiber loop sensors, 4 trip relays (7ms trip time) *, 1 system failure relay, 1BO, 2BI, Insertable sensors: AQ 06, AQ 07
AQ-101 | 12 point sensors, 1 fiber loop sensor (optional), 4 trip relays (7ms trip time) *, 1 watchdog relay, 1BO, 2BI,
Applicable sensors: AQ 01, AQ 01M, AQ 02, AQ 06 (optional), AQ 07 (optional)
AQ-101D | as AQ-101 only for DIN rail
AQ-101S | 12 point sensors, 3 trip relays (7ms trip time) *, 1 system failure relay, 3BO, 6BI,
Applicable sensors: AQ 01, AQ 01M, AQ 02
AQ 01 | a,b,c **Light sensor
AQ 01M | Portable sensor set
AQ 02 | light and pressure sensor
AQ 06 | plastic fibre sensor (5-50m length)
AQ 07 | fiber optic sensor (5-60m length)
*Optionally an electronic lock/trip relay available as normally closed contact
** a = 8,000 lux activation, b= 25,000 lux activation, c=50,000 lux activation